Skip to content

Swap a device

Applies to Enterprise ManagementField App Introduced in 1.0.2 Role: Administrator

When a sensor fails, runs out of battery, or is upgraded, Swap Device replaces it in one guided flow. The new sensor takes over the old one’s position, so its tags, trends, and alarms carry on without a gap. The old sensor is then deleted from SiteSync and your network server.

Use Swap Device when a new physical sensor goes into the same place as an old one: the old sensor failed, was damaged, ran out of battery, or is being upgraded. The measurement point stays the same and only the hardware behind it changes.

Swap DeviceDelete the old sensor and add the new one
Name, description, metadata, install location and photoCopied to the new sensorEntered again by hand
Tag pathThe new sensor takes it over, so anything reading those tags keeps workingSet up again for the new sensor
Old sensor’s downlinksListed on the new sensor, ready to resendLost with the old sensor
Record of the replacementWho, when and why, kept on the new sensorNone

If the new sensor is going somewhere else, or measuring something else, add it as a new device instead.

The new sensor takes the old sensor’s name and tag path. You can rename the sensor after the swap, and rename its tags too if you want.

The new sensor isWhat to do
New, and not in SiteSync yetScan its QR code or enter its keys. It’s added and swapped in together.
Already in SiteSync, such as a spare that was added or bulk uploaded ahead of timeChoose Choose an existing sensor instead and pick it from the list. No keys are needed.
  • You need edit access to the device’s site.
  • If the new sensor isn’t in SiteSync yet, have its DevEUI, JoinEUI (AppEUI), and AppKey to hand, or its QR code if you’re using the SiteSync mobile app.
  1. Open the old sensor’s page, choose Edit, then choose Swap Device. The Replace sensor screen opens.

  2. Choose the new sensor.

    • A new sensor: choose Scan QR code (in the mobile app), or enter its DevEUI, JoinEUI / AppEUI, and AppKey. It’s added with the old sensor’s device profile, site, and application.
    • A sensor already in SiteSync: choose Choose an existing sensor instead. The list shows sensors of the same device type at the same site, with their Device type, Site, and Last seen time. Untick Same device type and site only to see every sensor you can use. Search by name or DevEUI, or type a full DevEUI, and select the sensor.
    • If the sensor you choose already writes to its own tag path, a warning names that path. That path stops updating after the swap; its tag folder stays where it is.
  3. Choose Review replacement. Check what carries over, choose a Reason (Failed, Battery, Damaged, Upgrade, or Other), and add any Notes.

    • If the two sensors use different device profiles, a warning appears. Tick Use the old device’s profile to switch the new sensor to the old one’s profile, so its values fit the existing tags.
  4. Choose Replace sensor. Each step shows its own result as it runs:

    StepWhat happens
    Register the new sensorAdds it to SiteSync and your network server, only if you entered a new sensor
    Hand over the tag pathThe new sensor takes over the old one’s tags
    Copy device infoName, description, metadata and custom attributes, install location, and photo. A sensor from another site moves to the old sensor’s site.
    Record the replacement and delete the old sensorLinks the two sensors, then deletes the old one from SiteSync and your network server
    Record in the audit logAdds Device replaced and Device swapped in entries
  5. When every step is green, choose Done to open the new sensor’s page.

If a step fails, it shows the error and a Retry button. Each step checks what has already happened before it runs, so retrying is always safe. If registering or handing over the tag path fails, the later steps wait until you retry it. The old sensor is only deleted once every earlier step has succeeded, so its details are never lost halfway through.

Carries overDoesn’t carry over
The tag path, with its trends, history, and alarmsThe new sensor’s own previous tag folder, which is left in place
Name and descriptionThe old sensor’s audit, activity, and MQTT logs
Metadata and custom attributesThe In testing mark
Install location and photo
Site, when the new sensor was at another site
Device profile, if you chose Use the old device’s profile
The old sensor’s downlinks, under Previous device’s downlinks

The new sensor starts reporting into the old position from its first uplink.

To reconfigure the new sensor the way the old one was set up, see Downlink history.

The old sensor is deleted from SiteSync and from your network server. Its tags aren’t deleted, because the new sensor now writes to them.

These stay after the delete:

  • the replacement record, so the new sensor still shows which sensor it replaced, when, by whom, and why;
  • the old sensor’s downlinks, under Previous device’s downlinks on the new sensor;
  • the Device replaced and Device deleted entries in the audit log.

Sensors archived by swaps on an earlier version are deleted the same way, automatically, the next time someone signs in.

These entries appear under Devices in the audit log, and each can be turned on or off in the Audit Log settings:

EntryRecorded on
Device replacedThe old sensor
Device swapped inThe new sensor
Device deletedThe old sensor, when the swap deletes it
Device moved to another siteA sensor moved with Move Site
  • A swap can’t be undone. To put the original sensor back, add it again and swap it in; both swaps are kept in the history.
  • Adding a deleted sensor’s DevEUI back needs SiteSync module 1.95.21 or later. On earlier modules, wait until the module is upgraded.
  • Downlinks sent to the old sensor are listed for the new one under Previous device’s downlinks. See Downlink history.
Was this page helpful? Report incorrect documentation Last reviewed 2026-11-23